Home › Free calculators › Heat exchanger effectiveness–NTU rating
Free calculator

Heat exchanger effectiveness–NTU rating

Duty and outlet temperatures of an existing exchanger from its area and U — counter-current, shell-and-tube, cross flow and phase change.

Inputs

Units:
Hot stream
Cold stream
Exchanger

Results

Using this for a real decision? The Shell and Tube Heat Exchanger Performance and Fouling Excel tool checks every input, works in your units and prints a report for your files. USD 49 →

Need the full version for your plant?

The Shell and Tube Heat Exchanger Performance and Fouling Excel tool does everything here and more: actual U, fouling resistance and cleanliness from plant readings — with the duty lost to fouling, its yearly cost and the best cleaning interval. Print-ready report, any units, visible formulas, no macros.

Join PlantCalcKit — free

Be first to hear about new calculators, Excel tools and field guides — one short email when something new is ready. The calculators stay free with or without an account.

By joining you agree to our privacy policy. Unsubscribe or delete your details any time.

How this calculator works

The effectiveness–NTU method predicts how an existing exchanger performs when you know its area and U but not the outlet temperatures — for example at a new flow, a different inlet temperature or after fouling. The heat capacity rates C = ṁ·cp of the two streams give Cmin and the ratio Cr = Cmin/Cmax; NTU = UA/Cmin; the effectiveness ε follows from NTU, Cr and the flow arrangement; then the duty Q = ε·Cmin·(Thot,in − Tcold,in) and both outlet temperatures follow by heat balance.

Example: 20,000 kg/h of oil (cp 2.3 kJ/kg·K) at 150 °C cooled by 30,000 kg/h of water at 30 °C in a one-shell-pass exchanger of 60 m² with U = 350 W/m²·K: NTU = 1.64, Cr = 0.367, ε = 0.695, duty 1,065 kW, oil out at 66.7 °C and water out at 60.6 °C. The same area in true counter-flow would give 1,139 kW. The ε–NTU relations (Kays and London, as tabulated by Incropera) were checked against the open-source ht library for all seven arrangements at 88 points, agreeing to better than 0.0001 %.

The table shows how duty and outlet temperatures change with area at the same U — a quick way to see what an extra shell or a cleaning would give. To work out U and fouling from plant readings, use the LMTD calculator and the fouling calculator. References: Incropera and DeWitt, Fundamentals of Heat and Mass Transfer, Table 11.3; Kays and London, Compact Heat Exchangers; Perry's Chemical Engineers' Handbook §11.