Home › Free calculators › Heat exchanger duty and LMTD
Free calculator

Heat exchanger duty and LMTD

Duty, heat balance, LMTD, F correction factor and the area you need — for shell-and-tube, double-pipe and plate exchangers.

Inputs

Units:
Hot stream
Cold stream
Exchanger

Results

Using this for a real decision? The Shell and Tube Heat Exchanger Performance and Fouling Excel tool checks every input, works in your units and prints a report for your files. USD 49 →

Need the full version for your plant?

The Shell and Tube Heat Exchanger Performance and Fouling Excel tool does everything here and more: actual U, fouling resistance and cleanliness from plant readings — with the duty lost to fouling, its yearly cost and the best cleaning interval. Print-ready report, any units, visible formulas, no macros.

Join PlantCalcKit — free

Be first to hear about new calculators, Excel tools and field guides — one short email when something new is ready. The calculators stay free with or without an account.

By joining you agree to our privacy policy. Unsubscribe or delete your details any time.

How this calculator works

Duty on each side = flow × specific heat × temperature change; the average is used and the difference shows how well your readings close. The log-mean temperature difference (LMTD) is taken for counter-current flow (or co-current, if chosen). For shell-and-tube exchangers the LMTD is multiplied by the correction factor F, worked out from the two ratios R = hot range ÷ cold range and P = cold range ÷ (hot inlet − cold inlet). Area needed = duty ÷ (U × F × LMTD).

F is calculated exactly from the Bowman, Mueller and Nagle equations rather than read off a chart; for 2 shells in series the per-shell effectiveness method is used. As a check, the same exchanger is rated a second way by the effectiveness-NTU method and both routes give the same outlet temperatures.

The example is a heat-recovery exchanger: 50,000 kg/h of hot process liquid cooled from 120 to 70 °C while it heats 100,000 kg/h of water from 30 to 45 °C in a 1-2 shell-and-tube unit. Duty about 1,740 kW, LMTD 55.7 °C, F 0.957, so 72.5 m² is needed at U = 450 W/m²·K — the installed 80 m² gives about 10 % spare area.

F below 0.8 is a warning sign. On the steep part of the F curve, a small change in temperature needs a large change in area, and a real exchanger may not reach the duty. Use more shells in series, or a true counter-current design.

Limits: constant specific heats, no phase change (for condensers and reboilers, enter the duty-weighted values with care), the same U along the whole exchanger. References: Perry's Chemical Engineers' Handbook §11; Kern, Process Heat Transfer; Bowman, Mueller and Nagle, Trans. ASME 62 (1940); Heat Exchanger Design Handbook; TEMA Standards.

Learn the method step by step in Heat Exchangers Made Simple, Chapter 2. The first three chapters are free.
Related free calculators: Fouling and cleaning · Pump efficiency